Le capteur de température avec affichage ACL

MODEL Product Description
TE511 Sensor assembly c/w transmitter (sensor type 12 is standard) and LCD display ºC
TE512 Sensor assembly c/w transmitter (sensor type 12 is standard) and LCD display ºF
  CODE Style
B Duct mount
C Immersion c/w ½" NPT non-spring loaded fitting
D Duct average (copper)
E Strap-on
FD Duct average (flexible plenum rated cable)
G Glass
  CODE Boîtier (GES ABS enclosure is standard)
- ABS enclosure, standard (no code required, leave blank)
W PVC weatherproof box
 
CODE Secondary Sensor (Not available in flex and duct average configurations)
2 PT100-100 ohm Platinum, IEC 751, 385 Alpha, thin film
5 1801 ohm, NTC Thermistor, ±0.2°C
6 3000 ohm, NTC Thermistor, ±0.2 °C
7 10,000 ohm, type 3, NTC Thermistor, ±0.2 °C
9 100,000 ohm, NTC Thermistor, ±0.2 °C
12 PT1000-1000 ohm Platinum, IEC 751, 385 Alpha, thin film
13 1000 ohm Nickel
14 10,000 ohm, Type 3, NTC Thermistor, ±0.2°C c/w 11K shunt resistor
15 PT3000 PTC Platinum, ±0.2ºC
20 20,000 ohm, NTC Thermistor, ±0.2 °C
24 10,000 ohm, type 2, NTC Thermistor, ±0.2 °C   
  CODE

Probe Length

CODE

Copper Avg. (D)

CODE

Flex AVG. (FD)

A 50 mm (2") G 1800mm
(6')
A 1800mm
(6')
B 100 mm (4") H 3600mm
(12')
B 3600mm
(12')
C 150 mm (6") I 6100mm
(20')
C 6100mm
(20')
D 200 mm (8") J 7300mm
(24')
D 7300mm
(24')
E 300 mm (12")
F 450 mm (18")
  CODE Probe Material (not required for FD and G)
2 Stainless steel
3 Copper (rigid duct average only)
  CODE Transmitter Output Option 24 VAC/VDC
A 4 - 20 mA
D 0-5 VDC
E 0-10 VDC
  CODE Transmitter Range Option
1 0°C - 35°C (32°F - 95°F)
2 0°C - 50°C (32°F - 122°F)
3 0°C - 100°C (32°F - 212°F)
  Custom ranges available upon request.
TE511 C - 7 B 2 E 1