• LCD indication for both current and voltage
        models
  • Celsius or Fahrenheit display
  • Thermistor or Precision RTD sensing
        element
  • Integral Zero and Span adjustments
       (TE500)
  • Custom logo application
  • Modular design allows several option
       configurations
  • NEW functional and attractive enclosure
  • Installer-friendly wiring access
  • Highest quality double-sided FR4 PCB's




  • EXECUTIVE ENCLOSURE:

    The TE500 Series space temperature sensors are available in a wide selection of enclosures with a variety of options including LCD, setpoint adjustment and push button override capabilities.


    4-20mA Loop Power Supply 18 to 35 Vdc or 18 to 32 Vac (with 250 ohm load and no LCD) 22 to 35 Vdc or 22 to 32 Vac (with 250 ohm load and LCD)
    Minimum Loop Current 2 mA nominal (occurs with shorted sensor)
    Maximum Loop Current 22.5 mA nominal (occurs with open sensor)
    Maximum Loop Load >600 ohms at 24 Vac/dc with no LCD, > 325 ohms with LCD
    0-5 Vdc Power Supply 10 to 35 Vdc or 10 to 32 Vac, 15 Volts minimum with LCD
    0-10 Vdc Power Supply 15 to 35 Vdc or 15 to 32 Vac,
    Voltage Mode Maximum Current <3 mA with no LCD, 15 mA nominal with LCD
    Voltage Mode Maximum Output Limited to < 5.5 Vdc for 0-5 model and < 10.5 Vdc for 0-10 model & 0-5 with LCD
    Input Voltage Effect Negligible over specified operating range
    RFI Rejection Good RFI rejection of normal frequencies with standard installation
    Protection Circuitry Reverse voltage protected and output limited
    Output Signal 4-20mA current loop, 0-5 Vdc or 0-10 Vdc (factory configured)
    Transmitter Accuracy ±0.1% of span, including linearity
    Temperature Sensor Type 1000 ohm platinum RTD standard (class B, 385 Alpha, thin film)
    Temperature Calibration Three point with precision calibration standards
    Display Units °C or °F (Factory set)
    Display Range 0.0 to 35.0°C typical range for transmitter (other ranges available)
    Display Resolution 0.1°C or 0.1°F for display of 00.0 to 99.9
    Display Accuracy ±0.2°C or ±0.2°F over full range with respect to the output signal
    Display Update Rate 3 times per second
    Display Size 24 mm W x 11 mm H (0.95" x 0.45") three digit
    Operating Temperature 0 to 70°C (32 to 158°F)
    Operating Humidity 0 to 95% RH (non-condensing)
    Wiring Connections Two or three wires, screw terminal block (14 to 22 AWG)
    Manufacturing Process ISO 9001 Certified
    Internal Adjustments Clearly marked ZERO and SPAN pots
    Enclosure Size 71 mm W x 119 mm H x 32 mm D (2.8" x 4.7" x 1.25")
    universal back plates mount to any wall box or may be flush mounted
    Optional Slidepot 20 - 30K (L-R) standard, other values available
    Optional Switch Normally open pushbutton, 0.4 VA at 24 Vac/dc standard