| Pressure Ranges |
± 1 wc, ± 0.5 wc, ± 0.25 wc, ± 0.125 wc
± 250 Pa, ± 125 Pa, ± 60 Pa, ± 30 Pa |
| Calibration Accuracy |
± 1% F.S.O. (+/-2% F.S.O. for 0.125wc and 30 Pa ranges) |
| Measurement Types |
Differential (two ports) |
| Response Time |
.0.5 Sec |
| Thermal Effects |
< ±3.5% over compensated range |
| Compensated Range |
0 70° C (32 158° F) |
| Over Pressure |
100" W.C. (24.9 kPa) |
| Operating Conditions |
0 70° C (32 158° F), 10 90% RH non-condensing |
Power Supply (at transducer) |
15 - 27 Vac, 20 35 Vdc (non-isolated half-wave rectified) |
| Supply Current |
< 30mA (base model), 50mA (with alarm options), 70mA (with buzzer connected) |
| Input Voltage Effect |
Negligible over specified operating range |
| Protection Circuitry |
Reverse voltage protected and output limited |
| Output Signal |
4 20 mA (3-wire), 0 5 Vdc or 0 10 Vdc (3-wire), jumper selectable |
Current Output Drive Capability |
550 ohms |
Voltage Output Drive Capability |
2 Kohms minimum |
| Zero Adjustment |
Push button auto-zero (On device or Remote) |
| Optional Relay Output |
N.O. contact, 2.5 Amps @ 120 Vac, 2.5 Amps @ 30 Vdc |
| Relay Trip Point |
Adjustable from ZERO to SPAN via trimport |
| Relay Delay |
5 seconds on / 5 seconds off |
| Wiring Connections |
Screw terminal block (14 to 22 AWG) |
| Pressure Connections |
.1/8 ID Flexible tubing |
| Conduit Connection |
Access hole for 1/2 NPT conduit or cable gland |
| Display |
3.5 digit, 10 mm (0.4") digit height |
| Enclosure |
Executive Space, 2.8" W x 4.7" H x 1.25" D (71 x 119 x 32mm) |
| Weight |
.110 grams (3.9 oz) |