AC Current
Sensors CS-450/475 & SC-550/575
|

|


No field adjustment necessary, factory calibrated
Average measurement is equivalent to True RMS for pure sine waves for the CS-450 / SC-550 series.
True RMS measurement for sine waves or variable frequency drives for the CS-475 / SC-575 series.
Input / Output isolation via current transformer
Solid-state reliability
Small compact size
Solid, reliable mounting method
|
|



|

The
CS-450 / 475 and SC-550 / 575 series of AC current sensors are solid-state
transducers that convert a primary circuit current to a proportional
output signal. The sensors can monitor up to 200 Amps continuous and
feature three jumper selectable current ranges for the highest accuracy.
All sensors are factory calibrated to ensure better than 1% accuracy. The
CS-450 and the SC-550 are available with 0-5, 0-10 Vdc or 4 -20 mA
output signal types. The CS-475 and the SC-575 feature a true RMS 4-20 mA
loop-powered output signal. All models are CSA certified, UL approved and
CE compliant.
|
Input Current Ranges: |
Three field selectable ranges (See Below) |
|
AC Conductor
Hole: |
Split Core - 20mm (0.8") diameter
Split
Core - 24 x 19 mm (0.95 x 0.75") |
Enclosure Size
(H x W x D): |
Solid Core - 49 x 87 x 25 mm (1.95 x 3.45 x 1.0")
Split Core - 70 x 87 x 30 mm (2.75 x 3.45 x
1.2") |
|
Operating Humidity: |
0 to 95 % RH, non-condensing |
|
Protection Circuitry: |
Reverse voltage protected and output limited |
|
Wiring
Connections: |
Solid Core - Barrier strip
Split Core -
Screw terminals (14 to 22 AWG) |
|
Enclosure Material: |
UL 94 V-0 flammability rated ABS, Insulation class 600V |
|
Manufacturing: |
ISO 9001 Certified |
| CS-45X/SC-55X |
CS-475/SC-575 |
| Power Supply: |
0-5/0-10 Vdc models are self-powered, 4-20 mA model
requires 15-42 Vdc loop supply |
15-42 Vdc (loop powered) |
| Maximum Input
Current: |
10/20/50 Amp ranges-80/120/180 Amps inrush
50/100/200 Amp ranges-120/200/325 Amps inrush |
2/5/10 Amp ranges - 35/60/90 Amps inrush - (CS475 only)
10/20/50 Amp ranges - 80/120/200 Amps inrush
50/100/200 Amp ranges - 175/300/400 Amps inrush |
| Response Time: |
100 mS (0-90%) |
250 mS (0-90%) |
| Output Loading Error (0-5/0-10): |
Calibrated with 1 M ohm load, add 1.2% error with 100k ohm load |
N/A |
| Operating Temperature: |
0 to 40 °C (32 to 104 °F) |
0 to 40 °C (32 to 104 °F) |
| Output Signal & Accuracy |
0-5 Vdc, 0-10 Vdc or 4-20 mA
Better than ±1% FS on all 3 ranges |
4 to 20 mA represents 0 to 100% of current span
Better than ±1% FS on all three ranges |
 
         |