ETP-9500



Electronic to Pneumatic Transducer. This unit installs between the controller and a pneumatic device. It offers a low cost alternative for retrofit or new construction installations. It is available in 4-20ma and 0-10vdc 2wire or 3 wire versions, with or without an enclosure.














  • Direct connection to PCs for pneumatic control
  • Three-wire voltage modes and current ouptuts
  • Easily accessible wiring terminal blocks
  • Quick panel mounting with supplied snap-track
  • Floating point and pulse width modulation
       options
  • High accuracy with low hysteresis
  • Manual override available as standard or optional

  • Drifless operation with high
       repeatability
  • Input signal and power supply
       protection
  • AC/DC operation
  • Air filter supplied
  • Feedback signals available


  • ENC1



    Enclosure. Protects transducers or any automation or HVAC component. Twenty gauge metal, 2" diameter opening in cover for guage, two 7/8" diameter openings in the base ends for 1/2" EMT fitting for wiring connection, plastic snap-in covers for all openings.Size: 3.05" W x 3.3" H x 6" L.
    OUTPUT: Enclosure - small.












    EFP*



    Floating Point to Pneumatic Output. Input: Two Digital (relay, triac, or transistor) 9-24 VAC/VDC. Output: Jumper selectable 0 - 10, 0 - 15, or 0 - 20 psig air pressure. Rate of Change: 30, 45, 60, 90 sec., 2, 3, 6, and 8 minutes. Manual Override. Power: 24 VDC or 24 VAC @ 4A. Size: 4.0" L x 3.45" W x 1.875" H. Anodized aluminum manifold.
    OUTPUT: Pneumatic - Jumper Select 0-10, 0-15, 0-20 PSIG






    1





    1. EFP
    2. EFP2




    EPC*



    Analog to Pneumatic Output. Input: 0-5, 0-10 or 0-15 VDC/Infinite ohm, or 4-20 mA/250ohm. Output: 0-20 psig. Feedback: 0-5 VDC= selected output. Power: 24 VAC or VDC (50/60 HZ) @ 160 mA. Valve exhaust (EPC2), bleed-type in 41 scim (EPC), & dual Fail-safe (EPC3FS). Aluminum manifold. Gauge Optional
    OUTPUT: Pneumatic - Jumper Select 0-10, 0-15, 0-20 PSIG.






    1






    1. EPC
    2. EPC2/EPC2FS




    EPCB



    Analog to Pneumatic Output. Input: 0-5, 0-10 or 0-15 VDC/Infinite ohm, or 4-20 mA/250ohm. Output: 0-10, 0-15 and 0-20 psig. Feedback: 0-5 VDC= selected output. Power: 24 VAC or VDC (50/60 HZ) @ 180 mA. Controlled exhaust dual valve. Fail-safe model EPC2GFSB. Aluminum manifold. Rugged painted metal housing.
    OUTPUT: Pneumatic - Jumper Select 0-10, 0-15, 0-20 PSIG.












    EPW*



    Pulse Width Modulated to Pneumatic Output. Input: 0.1 - 10, 0.02-5, 0.023-6 or 0-10 sec. Duty cycle, 0.59 - 2.93, 0.1 - 25.5 sec. or 0 - 20 V phase cut. Trigger: 9 - 24 VAC/VDC. Output: 0 - 10, 0 - 15, 0 - 20 psig Manual override. Feedback: 0 - 5 VDC = range. Power: 24 VDC or 24 VAC @ 160mA. Valved exhaust or bleed type at 14, 41 & 73 scim, & Fail-Safe model
    OUTPUT: Pneumatic - Jumper Select 0-10, 0-15, 0-20 PSIG






    1





    1. EPW
    2. EPW2/EPW2FS




    MPOE



    Manual Pneumatic Override/Electric. Installs between controller and actuator to provide manual override in case of controller malfunction or during system checkout. PRV, terminal strip, switch and pneumatic connections mounted in twenty gauge metal bracket.
    OUTPUT: Pneumatic Override - Powered.












    PTP100



    100 psig Pressure to Analog Voltage or Current Output. Input: 20 - 100 psig air pressure. Output: 1 - 5 VDC, 2 - 10 VDC, 3 - 15 VDC, & 4 - 20mA @ 750 ohm load impedance. Power 24 VAC or 24 VDC @ 50mA max. Size: 3.75" L x 2.25" W x 1.5" H. Brass barbed fittings in anodized aluminum manifold.
    OUTPUT: Analog - Voltage or Current.












    PTP



    Pressure to Analog Voltage or Current Output. Input: 3 - 15, 3 - 30 or 0 - minus 7.5 psig air pressure. Output: 1 - 5 VDC, 2 - 10 VDC, 3 - 15 VDC, & 4 - 20mA @ 750ohm load impedance. Power: 24 VAC or 24 VDC @ 50mA max. Size: 3.75" L x 2.25" W x 1.5" H. Aluminum silver anodized manifold. Gauge available.
    OUTPUT: Analog - Voltage or Current.












    PTS4.1



    Floating Point to Pneumatic Output. Input: Two Digital (relay, triac, or transistor). Output: 0 - 10, 5 - 15, or 0 - 15 psig air pressure (jumper selectable). Rate of Change: 90 seconds. 1% Accuracy at room temperature. Power: 24 VDC or 24 VAC @ 4 VA. Size: 3.25" L x 2.25" W x 1.5" H. Anodized aluminum manifold. Gauge optional.
    OUTPUT: Pneumatic - 0-10, 5-15, or 0-15 PSIG.












    PXP100



    Analog to 100 psig Output. Input ranges/impedance: 0 - 5 VDC, 0 - 10 VDC or 0 - 15 VDC/10 Kohm, or 0 - 20mA/250 ohm. Output: 0 - 100 psig. Feedback: 0 - 5 VDC= 0 - 100 psig. Power: 24 VAC or VDC @ 150mA. Size: 3.25" L x 2.25" W x 1.5" H. Valved exhaust, anodized aluminum manifold.
    OUTPUT: Pneumatic - 0-100 PSIG.










    NOTES: [1] PWM - Pulse Width Modulated *Different models available

     NOTE:  For your convenience, we have provided selected product information in both HTML and PDF format.
      Product information available in PDF format is noted as the golden buttons shown on the right of the screen.

      To view PDF files, you will require Adobe Acrobat Reader software.
      If don't have this software installed, you may download it now: Simply click and follow the instructions.

      PDF files will be presented in a small Window at the upper left of your screen.
      If it is not visible you may have another PDF file open in the background: close the previously opened PDF and
      continue.



    HomeCompanyProductsISO 9000Client CenterContact UsLocationsStandardsSite Map
    Copyright ?Greystone Energy Systems Inc. 2003

    Privacy Statement