Environmental, industrial, and commercial Carbon Dioxide, Temperature and Humidity Sensor.



Executive Enclosure for CO2


To sense and transmit to any compatible electronic analog control, DDC/PLC controller or automation system for the control of ventilation equipment. Designed to meet ventilation requirements specified in ASHRAE Standard 62-1999.


  • Setup/calibration fully menu driven
        (requires LCD option).
  • Monitors CO2 over range 0-2000 PPM
        (factory default).
  • Field adjustable range from 0-1500 PPM up to
        10,000 PPM without re-calibration
  • NDIR single beam with patented self
        calibration algorithm.
  • Guaranteed 5 year calibration interval.
  • Optional LCD for displaying PPM, Temperature &
        Humidty levels and menu options.
  • Powered by either AC or DC source with no
       change to circuit required.
  • Choice of two field adjustable analog output
        signals, linearized over full range.
  • Easy to calibrate in the field



  • Carbon Dioxide/Temperature/Humidity Sensor - Product # CDD

    Product
    CDD1A7 & CDD1A8
    Range
    0-2000 ppm standard, programmable from 1500 up to 10,000 ppm
    Sensing Element
    Non-Dispersive Infrared Detector (NDIR)
    Standard Accuracy
    ±50 PPM or +3% of reading @22ºC(72ºF) when compared to certified calibration gas
    Operation Conditions
    0-50ºC (32-122ºF), 0-95% RH non-condensing
    Temperature Dependence
    0.2% FS per ºC
    Stability
    < 2 % FS over life of sensor (15 years typical)
    Output Signal
    (1A7)4-20 mA active (sourcing) or (1A8) 0-5Vdc or 0-10Vdc
    Output Drive Capability
    Current - 550 ohm max
    Voltage - 10 Kohm min
    Pressure Dependance
    0.13% of reading per mm Hg
    Alitiude Correction
    Programmable from 0-5000 ft in 500 ft increments
    Response Time
    2 minutes for 90% step change
    Warm-up Time
    2 minutes
    Power Supply
    20-30 Vac/dc (non-isolated half-wave rectified)
    Consumption
    125mA@24V maximum(70mA typical)
    Input Voltage Effect
    Negligible over specified operating range
    Protection Circuitry
    Reverse voltage protected and output limited
    LCD Display (Optional)
    LCD for displaying PPM level 0-2000, 0-100 %RH and 0-35ºC (32-95ºF) temperature, 1.3”w x 0.55”h (33 x 14 mm)
    Programming and Selection
    Via internal push-buttons and jumper
    Temperature Output Range
    0-35ºC (32-95ºF) or 0-50ºC (32-122ºF) Programmable
    Temperature Output Accuracy
    ±0.2ºC (±0.4ºF)
    Humidity Sensor
    Thermoset Polymer Based Capacitive
    Humidity Output Range
    0-100% RH
    Humidity Output Accuracy
    ±2%RH
    Humidity Response Time
    15 Seconds Typical
    Humidity Output Hysteresis
    ±2%RH
    Humidity Stability
    ±1%RH typical @ 50% RH in 5 years
    Wiring Connections
    Screw terminal block (14 to 22 AWG)
    External Dimensions
    Executive Space - 71mm W x 119mm H x 32mm D (2.8" x 4.7" x 1.25")


    HomeCompanyProductsISO 9000Client CenterContact UsLocationsStandardsSite Map
    Copyright © Greystone Energy Systems Inc. 2003