MODEL Product Description (Dual transmitter - Humidity and Temperature)
RH110 Space
RH210 Duct
RH310 Outside Air
  CODE Style
A Executive Space (RH110) ABS enclosure (RH210) ABS weatherproof enclosure (RH310)
B Designer space (RH110)
  CODE RH Accuracy
02 2%
03 3%
05 5%
  CODE Temperature Sensor
C PT1000-1000 ohm Platinum, IEC 751, 385 Alpha, thin film
L PT100-100 ohm Platinum, IEC 751, 385 Alpha, thin film (N/A on RH110)
  CODE Power Supply
1 24 VDC (RH110B)
2 24 VAC/DC (RH110A, RH210 and RH310)
  CODE Output Signal (RH and Temperature)
A 4 - 20mA (RH110A, RH110B, RH210, and RH310)
D 0 - 5 VDC (RH110A, RH210 and RH310)
E 0 - 10 VDC (RH110A, RH210 and RH310)
  CODE Temperature Transmitter Range
1 0°C - 35°C (32°F - 95°F)
2 0°C - 50°C (32°F - 122°F)
3 0°C - 100°C (32°F - 212°F)
6 -50°C - 50°C (-58°F - 122°F)
  CODE Options (RH110A Only)
AC Dual LCD display - Celsius
AF Dual LCD display - Fahrenheit
  Custom ranges available upon request.
RH210 A 03 C 2 A 1 -  
Greystone Energy Systems Inc., reserves the right to make design modifications without prior notice.

EXAMPLE:
Duct humidity c/w ABS enclosure, 3% accuracy temperature transmitter c/w 1000 ohm RTD, 24 VDC, 2 wire, 4 - 20mA output over 0°C - 35°C (32°F - 95°F)

RH210A03C2A1 


HomeCompanyProductsISO 9000Client CenterContact UsLocationsStandardsSite Map
Copyright © Greystone Energy Systems Inc. 2008