Carbon Dioxide w/ Temperature Sensor - Product # CDD
|
Product
|
CDD1A4 & CDD1A5
|
|
Range
|
0-2000 ppm
|
|
Sensing Element
|
Non-Dispersive Infrared Detector (NDIR)
|
|
Standard Accuracy
|
±50 PPM or +3% of reading @22ºC(72ºF) when compared to certified calibration gas
|
|
Operation Conditions
|
0-50ºC (32-122ºF), 0-95% RH non-condensing. -40-70ºC (-40-158ºF) in OSA Enclosure
|
|
Temperature Dependence
|
0.2% FS per ºC
|
|
Stability
|
< 2 % FS over life of sensor (15 years typical)
|
|
Output Signal
|
4-20 mA active (sourcing) or 0-5Vdc or 0-10Vdc, Model Specific
|
|
Output Drive Capability
|
Current - 550 ohm max Voltage - 2 Kohm min
|
|
Pressure Dependance |
0.13% of reading per mm Hg
|
|
Response Time |
2 minutes for 90% step change
|
|
Warm-up Time |
2 minutes
|
|
Power Supply |
20-30 Vac/dc (non-isolated half-wave rectified)
|
|
Consumption |
65mA@24V maximum(25mA typical)
|
|
Input Voltage Effect |
Negligible over specified operating range
|
|
Protection Circuitry |
Reverse voltage protected and output limited
|
|
LCD Display (Optional) |
LCD for displaying PPM level 0-2000, 1 ppm resolution, 1.3”w x 0.55”h (33 x 14 mm)
|
|
Programming and Selection |
Via internal push-buttons and jumper
|
|
Temperature Sensor |
Optional Thermistor or RTD
|
|
Wiring Connections |
Screw terminal block (14 to 22 AWG)
|
|
External Dimensions |
Executive Space - 71mm W x 119mm H x 32mm D (2.8" x 4.7" x 1.25")
|